Easy UPS for internal batteries | E3MUPS80KHBS | UPS 3M 80kVA 400V 3:3 Start-up 5x8
Easy UPS for internal batteries | E3MUPS80KHBS | UPS 3M 80kVA 400V 3:3 Start-up 5x8
NGN9,316,531.56
Availability:
In stock
Out of stock
Weight
339 kg

Product Description

Easy UPS for internal batteries | E3MUPS80KHBS | UPS 3M 80kVA 400V 3:3 Start-up 5x8

Easy-to-install, easy-to-connect, easy-to-use, and easy-to-service 80 kVA 3 phase UPS with advanced product features, robust electrical specifications and compact design making your business continuity easy. Ideal for small and medium data centers and other business critical applications, this UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management. This UPS is for internal batteries, but is supplied without batteries, so you can easily customize the battery runtime. For battery runtime details, see the runtime charts published under the Documents tab. Includes 5x8 start-up service.

Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
415 V
rated power in W 80 kW
rated power in VA 80 kVA
provided equipment Dust filter
Installation guide
Start-up service
Physical
colour White (RAL 9003)
height 197 cm
width 60 cm
depth 100 cm
net weight 339 kg
USB compatible Yes
Input
maximum input current 104 A
max short time withstand current 10 kA
input harmonic distortion Less than 3 % for full load
load power factor 0.5 leading to 0.5 lagging without derating
Input Power Factor at Full Load 0.99
input voltage limits 342...477 V
number of input connectors 1 hard wire 5-wire (3P + N + E)
network frequency 40...70 Hz
Output
Maximum configurable power in VA 80 kVA
Maximum configurable power in W 80 kW
output frequency 50 Hz sync to mains
60 Hz sync to mains
harmonic distortion Less than 3 %
output harmonic distortion < 3% linear load and < 5% non-linear load
output overload operation 10 minutes at 125% and 60 seconds at 150%
UPS type Double conversion online
Wave type Sine wave
bypass type Built-in static bypass
Conformance
product certifications CE
EAC
RCM
standards IEC 62040-1-1
IEC 62040-2
IEC 62040-3
ISTA 2B
Environmental
ambient air temperature for operation 0…40 °C
relative humidity 0…95 % non-condensing
operating altitude 0...1500 ft
ambient air temperature for storage -15…40 °C
storage Relative Humidity Non-condensing 0…95 %
storage altitude 0.00…4572.00 m
acoustic level 65 dBA
heat dissipation 14850 Btu/h
IP degree of protection IP20
Batteries & Runtime
battery type VRLA
battery voltage 240 V
number of battery filled slots 0
number of battery free slots 0
max current discharge 222 A
Communications & Management
alarm Audible and visible alarms prioritized by severity
control panel Touch screen LCD user interface
Packing Units
Package 1 Weight 387 kg
Package 1 Height 210.2 cm
Package 1 width 75 cm
Package 1 Length 112.5 cm